High Gain DC-DC and Active Power Decoupling Techniques for Photovoltaic Inverters

155955-Thumbnail Image.png
Description
The dissertation encompasses the transformer-less single phase PV inverters for both the string and microinverter applications. Two of the major challenge with such inverters include the presence of high-frequency common mode leakage current and double line frequency power decoupling with

The dissertation encompasses the transformer-less single phase PV inverters for both the string and microinverter applications. Two of the major challenge with such inverters include the presence of high-frequency common mode leakage current and double line frequency power decoupling with reliable capacitors without compromising converter power density. Two solutions are presented in this dissertation: half-bridge voltage swing (HBVS) and dynamic dc link (DDCL) inverters both of which completely eliminates the ground current through topological improvement. In addition, through active power decoupling technique, the capacitance requirement is reduced for both, thus achieving an all film-capacitor based solution with higher reliability. Also both the approaches are capable of supporting a wide range of power factor.

Moreover, wide band-gap devices (both SiC and GaN) are used for implementing their hardware prototypes. It enables the switching frequency to be high without compromising on the converter efficiency. Also it allows a reduced magnetic component size, further enabling a high power density solution, with power density far beyond the state-of-the art solutions.

Additionally, for the transformer-less microinverter application, another challenge is to achieve a very high gain DC-DC stage with a simultaneous high conversion efficiency. An extended duty ratio (EDR) boost converter which is a hybrid of switched capacitors and interleaved inductor technique, has been implemented for this purpose. It offers higher converter efficiency as most of the switches encounter lower voltage stress directly impacting switching loss; the input current being shared among all the interleaved converters (inherent sharing only in a limited duty ratio), the inductor conduction loss is reduced by a factor of the number of phases.

Further, the EDR boost converter has been studied for both discontinuous conduction mode (DCM) operations and operations with wide input/output voltage range in continuous conduction mode (CCM). A current sharing between its interleaved input phases is studied in detail to show that inherent sharing is possible for only in a limited duty ratio span, and modification of the duty ratio scheme is proposed to ensure equal current sharing over all the operating range for 3 phase EDR boost. All the analysis are validated with experimental results.
Date Created
2017
Agent

Robust Control of Wide Bandgap Power Electronics Device Enabled Smart Grid

155945-Thumbnail Image.png
Description
In recent years, wide bandgap (WBG) devices enable power converters with higher power density and higher efficiency. On the other hand, smart grid technologies are getting mature due to new battery technology and computer technology. In the near future, the

In recent years, wide bandgap (WBG) devices enable power converters with higher power density and higher efficiency. On the other hand, smart grid technologies are getting mature due to new battery technology and computer technology. In the near future, the two technologies will form the next generation of smart grid enabled by WBG devices. This dissertation deals with two applications: silicon carbide (SiC) device used for medium voltage level interface (7.2 kV to 240 V) and gallium nitride (GaN) device used for low voltage level interface (240 V/120 V). A 20 kW solid state transformer (SST) is designed with 6 kHz switching frequency SiC rectifier. Then three robust control design methods are proposed for each of its smart grid operation modes. In grid connected mode, a new LCL filter design method is proposed considering grid voltage THD, grid current THD and current regulation loop robust stability with respect to the grid impedance change. In grid islanded mode, µ synthesis method combined with variable structure control is used to design a robust controller for grid voltage regulation. For grid emergency mode, multivariable controller designed using H infinity synthesis method is proposed for accurate power sharing. Controller-hardware-in-the-loop (CHIL) testbed considering 7-SST system is setup with Real Time Digital Simulator (RTDS). The real TMS320F28335 DSP and Spartan 6 FPGA control board is used to interface a switching model SST in RTDS. And the proposed control methods are tested. For low voltage level application, a 3.3 kW smart grid hardware is built with 3 GaN inverters. The inverters are designed with the GaN device characterized using the proposed multi-function double pulse tester. The inverter is controlled by onboard TMS320F28379D dual core DSP with 200 kHz sampling frequency. Each inverter is tested to process 2.2 kW power with overall efficiency of 96.5 % at room temperature. The smart grid monitor system and fault interrupt devices (FID) based on Arduino Mega2560 are built and tested. The smart grid cooperates with GaN inverters through CAN bus communication. At last, the three GaN inverters smart grid achieved the function of grid connected to islanded mode smooth transition
Date Created
2017
Agent

Hybrid AC-High Voltage DC Grid Stability and Controls

155927-Thumbnail Image.png
Description
The growth of energy demands in recent years has been increasing faster than the expansion of transmission facility construction. This tendency cooperating with the continuous investing on the renewable energy resources drives the research, development, and construction of HVDC projects

The growth of energy demands in recent years has been increasing faster than the expansion of transmission facility construction. This tendency cooperating with the continuous investing on the renewable energy resources drives the research, development, and construction of HVDC projects to create a more reliable, affordable, and environmentally friendly power grid.

Constructing the hybrid AC-HVDC grid is a significant move in the development of the HVDC techniques; the form of dc system is evolving from the point-to-point stand-alone dc links to the embedded HVDC system and the multi-terminal HVDC (MTDC) system. The MTDC is a solution for the renewable energy interconnections, and the MTDC grids can improve the power system reliability, flexibility in economic dispatches, and converter/cable utilizing efficiencies.

The dissertation reviews the HVDC technologies, discusses the stability issues regarding the ac and HVDC connections, proposes a novel power oscillation control strategy to improve system stability, and develops a nonlinear voltage droop control strategy for the MTDC grid.

To verify the effectiveness the proposed power oscillation control strategy, a long distance paralleled AC-HVDC transmission test system is employed. Based on the PSCAD/EMTDC platform simulation results, the proposed power oscillation control strategy can improve the system dynamic performance and attenuate the power oscillations effectively.

To validate the nonlinear voltage droop control strategy, three droop controls schemes are designed according to the proposed nonlinear voltage droop control design procedures. These control schemes are tested in a hybrid AC-MTDC system. The hybrid AC-MTDC system, which is first proposed in this dissertation, consists of two ac grids, two wind farms and a five-terminal HVDC grid connecting them. Simulation studies are performed in the PSCAD/EMTDC platform. According to the simulation results, all the three design schemes have their unique salient features.
Date Created
2017
Agent

Insulation Coordination of Solid State Devices Connected Directly to the Electric Power Distribution System

155815-Thumbnail Image.png
Description
With the penetration of distributed renewable energy and the development of

semiconductor technology, power electronic devices could be utilized to interface re-

newable energy generation and the distribution power grid. However, when directly

connected to the power grid, the semiconductors inside the power

With the penetration of distributed renewable energy and the development of

semiconductor technology, power electronic devices could be utilized to interface re-

newable energy generation and the distribution power grid. However, when directly

connected to the power grid, the semiconductors inside the power electronic devices

could be vulnerable to the power system transient, especially to lightning strikes.

The work of this research focuses on the insulation coordination of power elec-

tronic devices connected directly to the power distribution system. The Solid State

Transformer (SST) in Future Renewable Electric Energy Delivery and Management

(FREEDM) system could be a good example for grid connected power electronic

devices. Simulations were conducted in Power Systems Computer Aided Design

(PSCAD) software. A simulation done to the FREEDM SST showed primary re-

sults which were then compare to simulation done to the grid-connected operating

Voltage Source Converter (VSC) to get more objective results.

Based on the simulation results, voltage surges caused by lightning strikes could

result in damage on the grid-connected electronic devices. Placing Metal Oxide Surge

Arresers (MOSA, also known as Metal Oxide Surge Varistor, MOV) at the front lter

could provide eective protection for those devices from power transient. Part of this

research work was published as a conference paper and was presented at CIGRE US

National Conference: Grid of the Future Symposium [1] and North American Power

Symposium [2].
Date Created
2017
Agent

Overview of Real-Time Simulation as a Supporting Effort to Smart-Grid Attainment

128030-Thumbnail Image.png
Description

The smart-grid approach undergoes many difficulties regarding the strategy that will enable its actual implementation. In this paper, an overview of real-time simulation technologies and their applicability to the smart-grid approach are presented as enabling steps toward the smart-grid’s actual

The smart-grid approach undergoes many difficulties regarding the strategy that will enable its actual implementation. In this paper, an overview of real-time simulation technologies and their applicability to the smart-grid approach are presented as enabling steps toward the smart-grid’s actual implementation. The objective of this work is to contribute with an introductory text for interested readers of real-time systems in the context of modern electric needs and trends. In addition, a comprehensive review of current applications of real-time simulation in electric systems is provided, together with the basis to understand real-time simulation and the topologies and hardware used to implement it. Furthermore, an overview of the evolution of real-time simulators in the industrial and academic background and its current challenges are introduced.

Date Created
2017-06-16
Agent

High Power Density, High Efficiency Single Phase Transformer-less Photovoltaic String Inverters

155749-Thumbnail Image.png
Description
Two major challenges in the transformer-less, single-phase PV string inverters are common mode leakage currents and double-line-frequency power decoupling. In the proposed doubly-grounded inverter topology with innovative active-power-decoupling approach, both of these issues are simultaneously addressed. The topology allows the

Two major challenges in the transformer-less, single-phase PV string inverters are common mode leakage currents and double-line-frequency power decoupling. In the proposed doubly-grounded inverter topology with innovative active-power-decoupling approach, both of these issues are simultaneously addressed. The topology allows the PV negative terminal to be directly connected to the neutral, thereby eliminating the common-mode ground-currents. The decoupling capacitance requirement is minimized by a dynamically-variable dc-link with large voltage swing, allowing an all-film-capacitor implementation. Furthermore, the use of wide-bandgap devices enables the converter operation at higher switching frequency, resulting in smaller magnetic components. The operating principles, design and optimization, and control methods are explained in detail, and compared with other transformer-less, active-decoupling topologies. A 3 kVA, 100 kHz single-phase hardware prototype at 400 V dc nominal input and 240 V ac output has been developed using SiC MOSFETs with only 45 μF/1100 V dc-link capacitance. The proposed doubly-grounded topology is then extended for split-phase PV inverter application which results in significant reduction in both the peak and RMS values of the boost stage inductor current and allows for easy design of zero voltage transition. A topological enhancement involving T-type dc-ac stage is also developed which takes advantage of the three-level switching states with reduced voltage stress on the main switches, lower switching loss and almost halved inductor current ripple.

In addition, this thesis also proposed two new schemes to improve the efficiency of conventional H-bridge inverter topology. The first scheme is to add an auxiliary zero-voltage-transition (ZVT) circuit to realize zero-voltage-switching (ZVS) for all the main switches and inherent zero-current-switching (ZCS) for the auxiliary switches. The advantages include the provision to implement zero state modulation schemes to decrease the inductor current THD, naturally adaptive auxiliary inductor current and elimination of need for large balancing capacitors. The second proposed scheme improves the system efficiency while still meeting a given THD requirement by implementing variable instantaneous switching frequency within a line frequency cycle. This scheme aims at minimizing the combined switching loss and inductor core loss by including different characteristics of the losses relative to the instantaneous switching frequency in the optimization process.
Date Created
2017
Agent

Risk-Based Dynamic Security Assessment of the Electricity Grid with High Penetration of Renewable Generation

155729-Thumbnail Image.png
Description
Electric power system security assessment is one of the most important requirements for operational and resource planning of the bulk power system ensuring safe operation of the power system for all credible contingencies. This deterministic approach usually provides a conservative

Electric power system security assessment is one of the most important requirements for operational and resource planning of the bulk power system ensuring safe operation of the power system for all credible contingencies. This deterministic approach usually provides a conservative criterion and can result in expensive bulk system expansion plans or conservative operating limits. Furthermore, with increased penetration of converter-based renewable generation in the electric grid, the dynamics of the grid are changing. In addition, the variability and intermittency associated with the renewable energy sources introduce uncertainty in the electricity grid. Since security margins have direct economic impact on the utilities; more clarity is required regarding the basis on which security decisions are made. The main objective of this work is to provide an approach for risk-based security assessment (RBSA) to define dynamic reliability standards in future electricity grids. RBSA provides a measure of the security of the power system that combines both the likelihood and the consequence of an event.

A novel approach to estimate the impact of transient stability is presented by modeling several important protection systems within the transient stability analysis. A robust operational metric to quantify the impact of transient instability event is proposed that incorporates the effort required to stabilize any transiently unstable event. The effect of converter-interfaced renewable energy injection on system reliability is investigated us-ing RBSA. A robust RBSA diagnostics tool is developed which provides an interactive user interface where the RBSA results and contingency ranking reports can be explored and compared based on specific user inputs without executing time domain simulations or risk calculations, hence providing a fast and robust approach for handling large time domain simulation and risk assessment data. The results show that RBSA can be used effectively in system planning to select security limits. Comparison of RBSA with deterministic methods show that RBSA not only provides less conservative results, it also illustrates the bases on which such security decisions are made. RBSA helps in identifying critical aspects of system reliability that is not possible using the deterministic reliability techniques.
Date Created
2017
Agent

Soft-Switching Techniques of Power Conversion System in Automotive Chargers

155580-Thumbnail Image.png
Description
This thesis investigates different unidirectional topologies for the on-board charger in an electric vehicle and proposes soft-switching solutions in both the AC/DC and DC/DC stage of the converter with a power rating of 3.3 kW. With an overview on different

This thesis investigates different unidirectional topologies for the on-board charger in an electric vehicle and proposes soft-switching solutions in both the AC/DC and DC/DC stage of the converter with a power rating of 3.3 kW. With an overview on different charger topologies and their applicability with respect to the target specification a soft-switching technique to reduce the switching losses of a single phase boost-type PFC is proposed. This work is followed by a modification to the popular soft-switching topology, the dual active bridge (DAB) converter for application requiring unidirectional power flow. The topology named as the semi-dual active bridge (S-DAB) is obtained by replacing the fully active (four switches) bridge on the load side of a DAB by a semi-active (two switches and two diodes) bridge. The operating principles, waveforms in different intervals and expression for power transfer, which differ significantly from the basic DAB topology, are presented in detail. The zero-voltage switching (ZVS) characteristics and requirements are analyzed in detail and compared to those of DAB. A small-signal model of the new configuration is also derived. The analysis and performance of S-DAB are validated through extensive simulation and experimental results from a hardware prototype.



Secondly, a low-loss auxiliary circuit for a power factor correction (PFC) circuit to achieve zero voltage transition is also proposed to improve the efficiency and operating frequency of the converter. The high dynamic energy generated in the switching node during turn-on is diverted by providing a parallel path through an auxiliary inductor and a transistor placed across the main inductor. The paper discusses the operating principles, design, and merits of the proposed scheme with hardware validation on a 3.3 kW/ 500 kHz PFC prototype. Modifications to the proposed zero voltage transition (ZVT) circuit is also investigated by implementing two topological variations. Firstly, an integrated magnetic structure is built combining the main inductor and auxiliary inductor in a single core reducing the total footprint of the circuit board. This improvement also reduces the size of the auxiliary capacitor required in the ZVT operation. The second modification redirects the ZVT energy from the input end to the DC link through additional half-bridge circuit and inductor. The half-bridge operating at constant 50% duty cycle simulates a switching leg of the following DC/DC stage of the converter. A hardware prototype of the above-mentioned PFC and DC/DC stage was developed and the operating principles were verified using the same.
Date Created
2017
Agent

Analytical approaches for identification and representation of critical protection systems in transient stability studies

155471-Thumbnail Image.png
Description
After a major disturbance, the power system response is highly dependent on protection schemes and system dynamics. Improving power systems situational awareness requires proper and simultaneous modeling of both protection schemes and dynamic characteristics in power systems analysis tools. Historical

After a major disturbance, the power system response is highly dependent on protection schemes and system dynamics. Improving power systems situational awareness requires proper and simultaneous modeling of both protection schemes and dynamic characteristics in power systems analysis tools. Historical information and ex-post analysis of blackouts reaffirm the critical role of protective devices in cascading events, thereby confirming the necessity to represent protective functions in transient stability studies. This dissertation is aimed at studying the importance of representing protective relays in power system dynamic studies. Although modeling all of the protective relays within transient stability studies may result in a better estimation of system behavior, representing, updating, and maintaining the protection system data becomes an insurmountable task. Inappropriate or outdated representation of the relays may result in incorrect assessment of the system behavior. This dissertation presents a systematic method to determine essential relays to be modeled in transient stability studies. The desired approach should identify protective relays that are critical for various operating conditions and contingencies. The results of the transient stability studies confirm that modeling only the identified critical protective relays is sufficient to capture system behavior for various operating conditions and precludes the need to model all of the protective relays. Moreover, this dissertation proposes a method that can be implemented to determine the appropriate location of out-of-step blocking relays. During unstable power swings, a generator or group of generators may accelerate or decelerate leading to voltage depression at the electrical center along with generator tripping. This voltage depression may cause protective relay mis-operation and unintentional separation of the system. In order to avoid unintentional islanding, the potentially mis-operating relays should be blocked from tripping with the use of out-of-step blocking schemes. Blocking these mis-operating relays, combined with an appropriate islanding scheme, help avoid a system wide collapse. The proposed method is tested on data from the Western Electricity Coordinating Council. A triple line outage of the California-Oregon Intertie is studied. The results show that the proposed method is able to successfully identify proper locations of out-of-step blocking scheme.
Date Created
2017
Agent

Real-Time Simulation of a Smart Inverter

155466-Thumbnail Image.png
Description
With the increasing penetration of Photovoltaic inverters, there is a necessity for recent PV inverters to have smart grid support features for increased power system reliability and security. The grid support features include voltage support, active and reactive power control.

With the increasing penetration of Photovoltaic inverters, there is a necessity for recent PV inverters to have smart grid support features for increased power system reliability and security. The grid support features include voltage support, active and reactive power control. These support features mean that inverters should have bidirectional power and communication capabilities. The inverter should be able to communicate with the grid utility and other inverter modules.

This thesis studies the real time simulation of smart inverters using PLECS Real Time Box. The real time simulation is performed as a Controller Hardware in the Loop (CHIL) real time simulation. In this thesis, the power stage of the smart inverter is emulated in the PLECS Real Time Box and the controller stage of the inverter is programmed in the Digital Signal Processor (DSP) connected to the real time box. The power stage emulated in the real time box and the controller implemented in the DSP form a closed loop smart inverter.

This smart inverter, with power stage and controller together, is then connected to an OPAL-RT simulator which emulates the power distribution system of the Arizona State University Poly campus. The smart inverter then sends and receives commands to supply power and support the grid. The results of the smart inverter with the PLECS Real time box and the smart inverter connected to an emulated distribution system are discussed under various conditions based on the commands received by the smart inverter.
Date Created
2017