Full metadata
Title
Investigating the costs and benefits of controllable inlet orifice hydraulic diameter in microchannel cooling devices
Description
Recent literature indicates potential benefits in microchannel cooling if an inlet orifice is used to suppress pressure oscillations that develop under two-phase conditions. This study investigates the costs and benefits of using an adjustable microchannel inlet orifice. The focus is on orifice effect during steady-state boiling and critical heat flux (CHF) in the channels using R134a in a pumped refrigerant loop (PRL). To change orifice size, a dam controlled with a micrometer was placed in front of 31 parallel microchannels. Each channel had a hydraulic diameter of 0.235 mm and a length of 1.33 cm. For steady state two-phase conditions, mass fluxes of 300 kg m-2 s-1 and 600 kg m-2 s-1were investigated. For orifice sizes with a hydraulic diameter to unrestricted hydraulic diameter (Dh:Dh,ur) ratio less than 35 percent, oscillations were reduced and wall temperatures fell up to 1.5 °C. Critical heat flux data were obtained for 7 orifice sizes with mass fluxes from 186 kg m-2 s-1 to 847 kg m-2 s-1. For all mass fluxes and inlet conditions tested, CHF values for a Dh:Dh,ur ratio of 1.8 percent became increasingly lower (up to 37 W cm-2 less) than those obtained with larger orifices. An optimum orifice size with Dh:Dh,ur of 35 percent emerged, offering up to 5 W cm-2 increase in CHF over unrestricted conditions at the highest mass flux tested, 847 kg m-2 s-1. These improvements in cooling ability with inlet orifices in place under both steady-state and impending CHF conditions are modest, leading to the conclusion that inlet orifices are only mildly effective at improving heat transfer coefficients. Stability of the PRL used for experimentation was also studied and improved. A vapor compression cycle's (VCC) proportional, integral, and derivative controller was found to adversely affect stability within the PRL and cause premature CHF. Replacing the VCC with an ice water heat sink maintained steady pumped loop system pressures and mass flow rates. The ice water heat sink was shown to have energy cost savings over the use of a directly coupled VCC for removing heat from the PRL.
Date Created
2012
Contributors
- Odom, Brent A (Author)
- Phelan, Patrick E (Thesis advisor)
- Herrmann, Marcus (Committee member)
- Trimble, Steve (Committee member)
- Tasooji, Amaneh (Committee member)
- Holcomb, Don (Committee member)
- Arizona State University (Publisher)
Topical Subject
Resource Type
Extent
xv, 86 p. : ill
Language
eng
Copyright Statement
In Copyright
Primary Member of
Peer-reviewed
No
Open Access
No
Handle
https://hdl.handle.net/2286/R.I.14524
Statement of Responsibility
by Brent A. Odom
Description Source
Viewed on Feb. 5, 2013
Level of coding
full
Note
thesis
Partial requirement for: Ph.D., Arizona State University, 2012
bibliography
Includes bibliographical references (p. 82-84)
Field of study: Mechanical engineering
System Created
- 2012-08-24 06:15:13
System Modified
- 2021-08-30 01:48:50
- 3 years 3 months ago
Additional Formats